TM 11520238T3
46
Change 4
412 SIGNAL NAME:
TAIL HEATER STATUS
MEMORY LOCATION: 002131
MEMORY DATA BIT(S):
4
(BINARY)
CONDITION:
(None)
SIGNAL FUNCTION:
Indicates tail rotor heater status.
REMARKS: From rotor blade deice controller through DASEC to FCC. Generates FD/LS message
TAIL ROTOR HEATER NOGO TAIL ROTOR.
PASS:
Location of fault if sixth digit on HOD is 1: ECS ICE DET circuit breaker, wiring from ECS ICE
DET circuit breaker to ice detector signal processor, ice detector signal processor, BLADE
DEICE circuit breaker, wiring from BLADE DEICE circuit breaker to BLADE DEICE
REMOTE CONTROL circuit breaker, BLADE DEICE REMOTE CONTROL circuit breaker,
wiring from BLADE DEICE REMOTE CONTROL circuit breaker to rotor blade deice
controller, ECS BLADE DEICE CONTR circuit breaker, wiring from ECS BLADE DEICE
CONTR circuit breaker to pilot ANTIICE panel, pilot ANTIICE panel, wiring from pilot
ANTIICE panel to rotor blade deice controller, rotor blade deice controller, wiring from
rotor blade deice controller to blade deice relay, blade deice relay, wiring from rotor rotor
blade deice controller to tail rotor slip ring assembly, tail rotor slip ring assembly, wiring from
tail rotor slip ring assembly to tail rotor blade, tail rotor blade. Troubleshoot wiring to isolate
fault (TM 11520238T8).
FAIL: Location of fault: rotor blade deice controller, wiring from rotor blade deice controller to slip
ring assembly, slip ring assembly, ,wiring from slip ring assembly to tail rotor blades, tail rotor
blades,wiring from rotor blade deice controller to DASEC, DASEC. Troubleshoot wiring to
isolate fault (TM 11520238T8).
413 SIGNAL NAME:
PNVS ANTIICE TO PEU (ACY) PNVS ANTIICE CMD (ACZ)
MEMORY LOCATION: 001632
MEMORY DATA BIT(S):
6
(BINARY)
CONDITION:
(None)
SIGNAL FUNCTION:
Indicates PNVS antiice selection.
REMARKS: From FCC through righthand (RH) FAB MRTU Type I to PNVS electronic unit (PEU).
PASS:
Location of fault if second digit on HOD is 2, 3, 6, or 7: wiring between PEU and TADS PNVS
turret assembly, and wiring between PEU and TEU. Troubleshoot wiring to isolate fault
(TM 15855265T).
FAIL: Location of fault: RH FAB MRTU Type I, wiring from RH FAB MRTU Type I to PEU, PEU.
Troubleshoot wiring to isolate fault (TM 15855265T).
414 SIGNAL NAME:
TADS ANTIICE TO TPS (ACY) TADS ANTIICE CMD (ACZ)
MEMORY LOCATION: 001220
MEMORY DATA BIT(S):
14
(BINARY)
CONDITION:
(None)
SIGNAL FUNCTION:
Indicates TADS antiice selection.
REMARKS: From FCC through LH FAB MRTU Type I to TADS power supply (TPS).
PASS:
If second digit on HOD is 4, 5, 6, or 7, go to paragraph 415.
FAIL: Location of fault: LH FAB MRTU Type I, wiring from LH FAB MRTU Type I to TPS, TPS, FCC.
Troubleshoot wiring to isolate fault (TM 11270476T).