TM 11520238T3
915
963 SIGNAL NAME:
PYLON 3 MRTU TYPE II STATUS WORD TERMINAL FLAG
MEMORY LOCATION: 001765
MEMORY DATA BIT(S):
19
(BINARY)
CONDITION:
(None)
SIGNAL FUNCTION:
Indicates PASS or FAIL status of MRTU internal selftests.
REMARKS: From PYLON 3 MRTU Type II to FCC.
PASS:
If first digit on HOD is 0, 2, 4, or 6, go to paragraph 971.
FAIL: Location of fault: go to paragraph 964.
964 SIGNAL NAME:
PYLON 3 MRTU TYPE II STATUS WORD BBC STATUS BIT
MEMORY LOCATION: 001765
MEMORY DATA BIT(S):
18
(BINARY)
CONDITION:
(None)
SIGNAL FUNCTION:
Indicates selftest status of the BBC.
REMARKS: From PYLON 3 MRTU Type II to FCC.
PASS:
If first digit on HOD is 2 or 6, go to paragraph 965.
FAIL: Location of fault: MUX R PYL INBD circuit breaker, wiring from MUX R PYL INBD circuit
breaker to PYLON 3 MRTU, PYLON 3 MRTU. Troubleshoot wiring to isolate fault
(TM 91230476202).
965 SIGNAL NAME:
PYLON 3 MRTU TYPE II STATUS WORD OUTPUT CLEAR
MEMORY LOCATION: 001765
MEMORY DATA BIT(S):
17
(BINARY)
CONDITION:
(None)
SIGNAL FUNCTION:
Indicates all MRTU outputs are cleared.
REMARKS: From PYLON 3 MRTU Type II to FCC.
PASS:
If first digit on HOD is 6, go to paragraph 966.
FAIL: Location of fault: MUX R PYL INBD circuit breaker, wiring from MUX R PYL INBD circuit
breaker to PYLON 3 MRTU, PYLON 3 MRTU. Troubleshoot wiring to isolate fault
(TM 91230476202).
966 SIGNAL NAME:
PYLON 3 MRTU TYPE II STATUS DISCRETE OUTPUT BIT
MEMORY LOCATION: 001765
MEMORY DATA BIT(S):
16
(BINARY)
CONDITION:
(None)
SIGNAL FUNCTION:
Indicates selftest status of 5 VDC discrete outputs.
REMARKS: From PYLON 2 MRTU Type II to FCC.
PASS:
If second digit on HOD is 1, 3, 5, or 7, go to paragraph 967.
FAIL: Location of fault: MUX R PYL INBD circuit breaker, wiring from MUX R PYL INBD circuit
breaker to PYLON 3 MRTU, PYLON 3 MRTU. Troubleshoot wiring to isolate fault
(TM 91230476202).
967 SIGNAL NAME:
PYLON 3 MRTU TYPE II STATUS DC ANALOG OUTPUT BIT
MEMORY LOCATION: 001765
MEMORY DATA BIT(S):
15
(BINARY)
CONDITION:
(None)
SIGNAL FUNCTION:
Indicates state of output DC analog circuits.
REMARKS: From PYLON 3 MRTU Type II to FCC.
PASS:
If second digit on HOD is 3 or 7, go to paragraph 968.
FAIL: Location of fault: MUX R PYL INBD circuit breaker, wiring from MUX R PYL INBD circuit
breaker to PYLON 3 MRTU, PYLON 3 MRTU. Troubleshoot wiring to isolate fault
(TM 91230476202).