TM 1–1520–238–T–3Change 411–511–10 SIGNAL NAME:PYLON POS (ACY) PYLON POS AID (ACZ)MEMORY LOCATION: 001465MEMORY DATA BIT(S):4–19(SCALAR)CONDITION:Monitor HOD while using the PYLON ACTG SW; memory location response shouldincrease when up (flight stow) is selected and decrease, then go negative when down(ground stow) is selected.SIGNAL FUNCTION:Indicates pylon position to RHE.REMARKS: From FCC to RHE. Pylon elevation positioning data.PASS:If CONDITION has been met, go to paragraph 11–11.FAIL: Location of fault: wiring from external stores elevation controller to pylon actuator controller.Troubleshoot wiring to isolate fault (TM 9–1427–475–20).11–11 SIGNAL NAME:PYLN 1 POS (ACY) P1 POSITION (ACZ)MEMORY LOCATION: 001655MEMORY DATA BIT(S):4–19(SCALAR)CONDITION:Monitor HOD while using the PYLON ACTG SW; memory location response shouldincrease when up (flight stow) is selected and decrease, then go negative when down(ground stow) is selected.SIGNAL FUNCTION:Indicates pylon 1 position.REMARKS: From pylon actuator controller (PAC) 1 through LH outboard (OUTBD) MRTU Type II toFCC. Pylon 1 elevation positioning data.PASS:If CONDITION has been met, go to paragraph 11–12.FAIL: Location of fault: external stores elevation controller, wiring from external stores controller topylon actuator controller 1, pylon actuator controller 1, wiring from pylon actuator controller 1 toLH OUTBD MRTU Type II, LH OUTBD MRTU Type II. Troubleshoot wiring to isolate fault(TM 9–1090–208–23–2).11–12 SIGNAL NAME:PAC 1 STATMEMORY LOCATION: 001654MEMORY DATA BIT(S):4–19(SCALAR)CONDITION:(None)SIGNAL FUNCTION:Generates PYLN ACTUATOR CONTROLLER NO–GO LT OUTBD FD/LSmessage.REMARKS: From PAC through LH OUTBD MRTU Type II to FCC.PASS:If sixth digit on HOD is 0, go to paragraph 11–13.FAIL: Location of fault: pylon actuator controller 1, pylon actuator controller 1, wiring from pylonactuator controller 1 to LH OUTBD MRTU Type II, LH OUTBD MRTU Type II. Troubleshootwiring to isolate fault (TM 9–1090–208–23–2).11–13 SIGNAL NAME:PYLN 1 STAT (ACY) P1 COM STAT (ACZ)MEMORY LOCATION: 001434MEMORY DATA BIT(S):19(BINARY)CONDITION:(None)SIGNAL FUNCTION:Generates PYLON NO GO FD/LS message.REMARKS: From FCC to RHE. Pylon 1 status to RHE.PASS:If first digit on HOD is 0, 2, 4, or 6, go to paragraph 11–27.FAIL: Location of fault: replace RHE (TM 9–1427–475–20).
Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business