TM 1-1520-238-T-5
7143
749.
SHAFT DRIVEN COMP INDICATOR REMAINS LIGHTED AFTER APU START CYCLE (cont)
749
7. Check SDC overboard vent for very strong,
steady air discharge.
Is very strong, steady air discharge present?
YES
Replace SDC total pressure
sense line filter and surge valve
pressure filter
(TM 1-1520-238-23).
If filters have been replaced
once, replace SDC assembly
(TM 1-1520-238-23).
NO
Replace SDC inlet throttle valve
(TM 1-1520-238-23).
8. Shutdown APU (TM 1-1520-238-23).
(AAG) Check for open between P2172 and
GS541F.
(ABC) Check for open between P2172 and
GS543F.
Does open exist?
YES
Repair open wire.
Go to paragraph 745.
NO
Go to step 9.
9. Check for open between (A402)J148 and
P2171.
Does open exist?
YES
Go to step 10.
NO
Refer to TM 1-1520-238-T-6 to
troubleshoot circuit protection
system (dc emergency bus
pilot station).
10. Check for open between (A402):
K21/2A3 and K21/2A2.
Does open exist?
YES
Replace relay (A402)K21/2.
(TM 1-1520-238-23).
NO
Repair open wire between:
P442B3 and P2171.
(A402):
J148 and TB26D,
XK21/2A3 and J5B3,
TB26B and XK21/2A2.
Go to paragraph 745.
11. With APU running and air flowing from ECS
vents, detach wire from GS541K.
Is SHAFT DRIVEN COMP indicator on?
YES
Go to step 12.
NO
Replace SDC outlet pressure
switch (TM 1-1520-238-23).
12. Check for short to ground between:
P440B15 and P1838,
P442B1 and P13233.
(A402):
J5B1 and TB212S,
TB212R and J16B15.
Does short exist?
YES
Repair shorted wire.
Go to paragraph 745.
NO
Replace pilot caution/warning
panel (TM 1-1520-238-23).
END OF TASK