512 SIGNAL NAME:
CPG HAS GUN
MEMORY LOCATION: 001530
MEMORY DATA BIT(S):
14
(BINARY)
CONDITION:
(None)
SIGNAL FUNCTION:
Indicates whether CPG has control of gun.
REMARKS: From GTCB through RH FAB MRTU Type I to FCC.
PASS:
If second digit displayed on HOD is 4, 5, 6, or 7, go to paragraph 513.
FAIL: Location of fault: CPG FCP, wiring from CPG FCP to GTCB, GTCB, wiring from GTCB to RH
FAB MRTU Type I, RH FAB MRTU Type I. Troubleshoot wiring to isolate fault
(TM 91090208232).
513 SIGNAL NAME:
CPG SIGHT SELECT SW
MEMORY LOCATION: 001074
MEMORY DATA BIT(S):
46
(OCTAL)
CONDITION:
If the fifth digit displayed on HOD is 0 or 1=HMD/TADS (Chapter 15, paragraph 155)
If the fifth digit displayed on HOD is 2 or 3=TADS (Chapter 15, paragraph 155)
If the sixth digit displayed on HOD is 1=NVS (Chapter 10, paragraph 106)
If the sixth digit displayed on HOD is 1 and the fifth digit displayed on HOD is 2 or 3
=HMD (Chapter 7, paragraph 756)
SIGNAL FUNCTION:
Indicates position of CPG SIGHT SEL switch.
REMARKS: From CPG FCP through LH FAB MRTU Type I to FCC.
PASS:
If CONDITION displayed on HOD corresponds to CPG SIGHT SEL switch position, refer to
appropriate chapter and paragraph as listed under CONDITION.
FAIL: Location of fault: CPG FCP, wiring from CPG FCP to LH FAB MRTU Type I, LH FAB MRTU
Type I. Troubleshoot wiring to isolate fault (TM 91230476202).
514 SIGNAL NAME:
CPG ACQ SELECT SW
MEMORY LOCATION: 001074
MEMORY DATA BIT(S):
79
(OCTAL)
CONDITION:
If the fourth digit displayed on HOD is 0 or 1=PHS
(Chapter 7, paragraph 738)
If the fourth digit displayed on HOD is2 or 3=FXD
(Chapter 10, paragraph 1030)
If the fourth digit displayed on HOD is 4 or 5=TGT
(Chapter 16, paragraph 1623)
If the fourth digit displayed on HOD is 6 or 7=NAV
(Chapter 20, paragraph 2037)
If the fifth digit displayed on HOD is 1, 3, 5, or 7=GHS
(Chapter 7, paragraph 730)
If the fifth digit displayed on HOD is 1, 3, 5, or 7 and the fourth digit displayed on HOD
is 2 or 3=MSL SKR (Chapter 8, paragraph 810)
If the fifth digit displayed on HOD is 1, 3, 5, or 7 and the fourth digit displayed on HOD
is 4 or 5=TADS (Chapter 15, paragraph 156)
SIGNAL FUNCTION:
Enables cueing or slaving to selected CPG line of sight (LOS).
REMARKS: From CPG FCP through LH FAB MRTU Type I to FCC.
PASS:
If CONDITION displayed on HOD corresponds to selected CPG ACQ SEL switch position, go
to appropriate chapter and paragraph as listed under CONDITION.
FAIL: Location of fault: CPG FCP, wiring from CPG FCP to LH FAB MRTU Type I, LH FAB MRTU
Type I. Troubleshoot wiring to isolate fault (TM 91230476202).