TM 1-1520-238-T-6
9290
997.
CPG COLLECTIVE STICK EDGE-LIGHT IS NOT LIGHTED
997
Tools:
Nomenclature
Part Number
Tool Kit, Electrical
SC518099CLA06
Repairers
Multimeter, Digital
AN/PSM-45
Personnel Required:
68X
Armament/Electrical Systems Repairer
One person to assist
References:
TM 1-1520-238-23
Equipment Conditions:
Ref
Condition
TM 1-1520-238-23
Non-transparent barrier
removed
WARNING
Turn off power before detaching or
attaching wires and connectors. High
current 28 VDC or 115 VAC is present.
Failure to do so could result in death or
serious injury.
1. On CPG INTR LT panel, place L CSL control to
BRT. Check for 5 VDC between (A326):
J12-B1 and J12-B2.
Is voltage present?
YES
Go to step 3.
NO
Go to step 2.
2. Check for open between (A326):
J12-B1 and TB1-47-C,
J12-B2 and TB1-47-J.
Does open exist?
YES
Repair open wire.
Go to paragraph 980.
NO
Go to paragraph 9132 to
troubleshoot CPG edge-lights.
3. Check for open between:
P465-B1 and J108-a,
P465-B2 and J108-Z.
Does open exist?
YES
Repair open wire.
Go to paragraph 980.
NO
Replace CPG collective stick
edge-light panel
(TM 1-1520-238-23).
END OF TASK