TM 1-1520-238-T-6
9449
9195. POWER XFMR RECT 2 CIRCUIT BREAKER (CB4) DOES NOT STAY CLOSED OR
9195
CONTINUITY DOES NOT EXIST BETWEEN: P4-A AND P4-D, P4-B AND P4-E,
P4-C AND P4-F
Tools:
Nomenclature
Part Number
Tool Kit, Electrical
SC518099CLA06
Repairers
Multimeter, Digital
AN/PSM-45
Personnel Required:
68X
Armament/Electrical Systems Repairer
References:
TM 1-1520-238-23
WARNING
Turn off power before detaching or
attaching wires and connectors. High
current 28 VDC or 115 VAC is present.
Failure to do so could result in death or
serious injury.
1. On pilot ELEC PWR panel set BATT/EXT PWR
switch to EXT PWR.
Does POWER XFMR RECT 2 circuit breaker
(CB4) stay closed?
YES
Go to step 4.
NO
Go to step 2.
2. Open CB4. Set BATT/EXT PWR switch to OFF.
Check for short between:
P4-D and ground,
P4-E and ground,
P4-F and ground.
Does short exist?
YES
Go to step 3.
NO
Go to paragraph 912 to
troubleshoot ac electrical power
generation.
3. Detach wire at CB4-A2, CB4-B2, and CB4-C2.
Check for short between:
P4-D and ground,
P4-E and ground,
P4-F and ground.
Does short exist?
YES
Repair shorted wire.
Go to paragraph 9189.
NO
Replace POWER XFMR RECT
2 circuit breaker (CB4)
(TM 1-1520-238-23).
4. Set BATT/EXT PWR switch to OFF. Check for
open between:
P4-A and CB4-A1,
P4-B and CB4-B1,
P4-C and CB4-C1,
P4-D and CB4-A2,
P4-E and CB4-B2,
P4-F and CB4-C2.
Does open exist?
YES
Repair open wire.
Go to paragraph 9189.
NO
Replace POWER XFMR RECT
2 circuit breaker (CB4)
(TM 1-1520-238-23).
END OF TASK