TM 1-1520-238-T-6
9465
9206. CIRCUIT PROTECTION SYSTEM (DC ESSENTIAL BUS 1 PILOT STATION)
9206
MAINTENANCE OPERATIONAL CHECK (cont)
M69218
ECS WSHLD
WPR
ECS CANOPY
ANTIICE CONTR
STAB MAN DC
ECS ENG
ANTIICE
POWER BATT
CHGR DC
CBR BLWR
Figure 9173.
Pilot Aft Circuit Breaker Panel
Task
Result
i. Check that circuit breakers closed in step g.
remain closed.
If STAB MAN DC circuit breaker (CB6) does not stay
closed, go to paragraph 9209.
If ECS CANOPY ANTI-ICE CONTR circuit breaker
(CB70) does not stay closed, go to paragraph 9210.
If ECS WSHLD WPR circuit breaker (CB71) does not
stay closed, go to paragraph 9211.
If ECS ENG ANTI-ICE circuit breaker (CB67) does
not stay closed, go to paragraph 9212.
If POWER BATT CHGR DC circuit breaker (CB5)
does not stay closed, go to paragraph 9213.
If CBR BLWR circuit breaker (CB94) does not stay
closed, go to paragraph 9214.
j. On pilot ELEC PWR panel (fig. 9172), set
BATT/EXT PWR switch to OFF.
k. On electrical power distribution box, detach
P1 and P2.
l. On pilot ELEC PWR panel, set BATT/EXT
PWR switch to EXT PWR.
m. Check for 28 VDC at P2-g.
If 28 VDC is not present, go to paragraph 9209.
n. Check for 28 VDC at P1-3.
If 28 VDC is not present, go to paragraph 9210.
o. Check for 28 VDC at P2-b.
If 28 VDC is not present, go to paragraph 9211.
p. Check for 28 VDC at P1-4.
If 28 VDC is not present, go to paragraph 9212.