TM 1-1520-238-T-7
Change 5
10185
1063. PILOT FUEL XFER ADVISORY LIGHT IS NOT LIGHTED (ADA)
1063
Tools:
Nomenclature
Part Number
Tool Kit, Electrical
SC518099CLA06
Repairers
Multimeter, Digital
AN/PSM-45
Personnel Required:
68X
Armament/Electrical Systems Repairer
One person to assist
References:
TM 1-1520-238-23
Equipment Conditions:
Ref
Condition
TM 1-1520-238-23
Access provisions
L40 door removed
WARNING
Turn off power before detaching or
attaching wires and connectors. High
current 28 VDC or 115 VAC is present.
Failure to do so could result in death or
serious injury.
1. Check for open between P748b and P748c.
Does open exist?
YES
Go to step 4.
NO
Go to step 2.
2. Check for 28 VDC at P748d.
Is voltage present?
YES
Replace multichannel dimming
controller
(TM 1-1520-238-23).
NO
Go to step 3.
3. Check for open between P748d and P197B9.
Does open exist?
YES
Repair open wire.
Go to paragraph 1047.
NO
Replace pilot FUEL panel
(TM 1-1520-238-23).
4. Check for open between:
P748b and DS19 SP2,
P748c and DS19 SP1.
Does open exist?
YES
Repair open wire.
Go to paragraph 1047.
NO
Replace pilot FUEL XFER
advisory light (DS19)
(TM 1-1520-238-23).
END OF TASK