MAIN ROTOR BLADE SPAR TO SPAR DEBOND REPAIR (AVIM) continued
NOTE
Press controller M key once to scroll
through each menu item. Use controller
up and down keys to set operational val-
ues.
u. Set-up controller (26) operation menu.
(1) Use up key (27) and down key (28) to set set
point (rP) to 180 F (88.2 C).
(2) Press M key (29), use up key (27) and down
key (28) to set proportional band (Pb1) to 25
F (-3.9 C).
(3) Press M key (29), use up key (27) and down
key (28) to set reset/integral (rE1) to 0.08.
(4) Press M key (29), use up key (27) and down
key (28) to set rate/derivative (rA1) to 0.08.
(5) Press M key (29), use up key (27) and down
key (28) to set cycle time (Ct1) to 6.5 sec-
onds.
(6) Press M key (29), use up key (27) and down
key (28) to set alarm low (ALO) to -10 F
(-23.3 C).
(7) Press M key (29), use up key (27) and down
key (28) to set alarm high (AH1) to 10 F
(-12.2 C).
(8) Press M key (29), use up key (27) and down
key (28) to set calibration offset (CAL) to -1 F
(-18.3 C).
(9) Press M key (29), use up key (27) and
down key (28) to set auto-tune (AUt) to 0.
(10) Press M key (29) to return to beginning
menu.