9224. IR JAM XMTR CIRCUIT BREAKER (CB66) DOES NOT STAY CLOSED
9224
OR 28 VDC IS NOT PRESENT AT P2-h
Tools:
Nomenclature
Part Number
Tool Kit, Electrical
SC518099CLA06
Repairers
Multimeter, Digital
AN/PSM-45
Personnel Required:
68X
Armament/Electrical Systems Repairer
One person to assist
References:
TM 1-1520-238-23
TM 11-1520-238-23-2
WARNING
Turn off power before detaching or
attaching wires and connectors. High
current 28 VDC or 115 VAC is present.
Failure to do so could result in death or
serious injury.
1. On pilot ELEC PWR panel, set BATT/EXT PWR
switch to EXT PWR.
Does IR JAM XMTR circuit breaker (CB66)
stay closed?
YES
Go to step 4.
NO
Go to step 2.
2. Open CB66 and set BATT/EXT PWR switch to
OFF. Check for short between P2-h and ground.
Does short exist?
YES
Go to step 3.
NO
Refer to TM 11-1520-238-23-2
to troubleshoot IR jammer.
3. Detach wire at CB66-2. Check for short between
P2-h and ground.
Does short exist?
YES
Repair shorted wire between
CB66-2 and P2-h.
Go to paragraph 9220.
NO
Replace IR JAM XMTR circuit
breaker (CB66)
(TM 1-1520-238-23).
4. Set BATT/EXT PWR switch to OFF. Check for
open between:
CB66-1 and CB46-1,
CB66-2 and P2-h.
Does open exist?
YES
Repair open wire.
Go to paragraph 9220.
NO
Replace IR JAM XMTR circuit
breaker (CB66)
(TM 1-1520-238-23).
END OF TASK