MUX SYSTEM INTERACTIVE FD/LS
48
CHECK (cont)
TASK
RESULT
NOTE
If this FD/LS check is to be followed by a
MULTIPLEX SYSTEM OPERATIONAL
CHECK (TM 9-1230-476-20-2), omit step 3.
3. Perform SYSTEMS POWER DOWN (para 32) if
power no longer required.
FD/LS NOGO
DISPLAY
CORRECTIVE ACTION
TYPE IIIA MRTU
NOGO CPG
COMPARTMENT
Troubleshoot wiring to isolate
fault (TM 9-1230-476-20-2). If
troubleshooting does not
remove NOGO, replace
Type IIIA multiplex remote
terminal unit (MRTU)
(TM 9-1230-476-20-1). If
replacement does not
remove NOGO, replace
FCC.
TYPE IIIA MRTU RT
BUS NOGO CPG
COMPARTMENT
(ACZ)
Troubleshoot wiring to isolate
fault (TM 9-1230-476-20-2).
TYPE IIIA MRTU LT
BUS NOGO CPG
COMPARTMENT
(ACZ)
Troubleshoot wiring to isolate
fault (TM 9-1230-476-20-2).
TYPE I MRTU NOGO
LH FAB
Troubleshoot wiring to isolate
fault (TM 9-1230-476-20-2). If
troubleshooting does not
remove NOGO, replace
Type I MRTU
(TM 9-1230-476-20-1). If
replacement does not
remove NOGO, replace
FCC (TM 9-1230-476-20-1).
TYPE I MRTU RT
BUS NOGO LH FAB
(ACZ)
Troubleshoot wiring to isolate
fault (TM 9-1230-476-20-2).